DeltaUPS-MIB

DeltaUPS-MIB Download

MIBs list

IPHost Network Monitor offer an easy way of SNMP monitoring your Belkin Servers, Routers, Switches, Bridges, Firewalls, Repeaters.

OID list for DeltaUPS-MIB

dupsIdentManufacturer
The name of the UPS manufacturer.
dupsIdentModel
The UPS Model designation.
dupsIdentUPSSoftwareVersion
The UPS firmware/software version(s). This variable may or may not has the same value as upsIdentAgentSoftwareVersion in some implementations.
dupsIdentAgentSoftwareVersion
The UPS agent software version. This variable may or may not has the same value as upsIdentUPSSoftwareVersion in some implementations.
dupsIdentName
A string identifying the UPS. This object should be set by the administrator.
dupsAttachedDevices
A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.
dupsRatingOutputVA
The magnitude of the nominal output VA rating.
dupsRatingOutputVoltage
The magnitude of the nominal output voltage rating.
dupsRatingOutputFrequency
The magnitude of the nominal output frequency rating.
dupsRatingInputVoltage
The magnitude of the nominal input voltage rating.
dupsRatingInputFrequency
The magnitude of the nominal input frequency rating.
dupsRatingBatteryVoltage
The magnitude of the nominal battery voltage rating.
dupsLowTransferVoltUpBound
The minimum input line voltage upper bound allowed before the UPS system transfers to battery backup.
dupsLowTransferVoltLowBound
The minimum input line voltage lower bound allowed before the UPS system transfers to battery backup.
dupsHighTransferVoltUpBound
The maximum input line voltage upper bound allowed before the UPS system transfers to battery backup.
dupsHighTransferVoltLowBound
The maximum input line voltage lower bound allowed before the UPS system transfers to battery backup.
dupsLowBattTime
Minutes, time from low battery to low battery shutdown.
dupsOutletRelays
Number of outlet relay. If it is 0, the function is not available for the UPS.
dupsType
Indicate the UPS type.
dupsShutdownType
This object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the ...
dupsAutoReboot
If ON, UPS system will restart after a shutdown. If OFF, UPS must be restarted manually.
dupsShutdownAction
If the value is greater than 0 the UPS performs shutdown action that defined by ShutdownType after the seconds. 0, aborted.
dupsShutdownRestart
UPS will restart after the indicated number of minutes. -1, aborted.
dupsSetOutletRelay
Indicate which outlet relay, from 1,2,3... .
dupsRelayOffDelay
Turn the relay off after the seconds. The relay was indicated by SetOutletRelay.
dupsRelayOnDelay
Turn the relay on after the seconds. The relay was indicated by SetOutletRelay.
dupsConfigBuzzerAlarm
UPS will keep silence but will alarm again when next power event is occurred
dupsConfigBuzzerState
If it is disabled then the UPS is always muted.
dupsConfigSensitivity
The seneitivity of the UPS to utility line abnormalities or noises.
dupsConfigLowVoltageTransferPoint
The minimum input line voltage allowed before the UPS system transfers to battery backup.
dupsConfigHighVoltageTransferPoint
The maximum line voltage allowed before the UPS system transfers to battery backup.
dupsConfigShutdownOSDelay
The operating system shutdown delay time when the input power fail. -1 will disable this option.
dupsConfigUPSBootDelay
Delay the UPS startup after power restores. The power quality may not stable when power restores, this feature let the UPS wait a period of time to startup the system.
dupsInputNumLines
The number of input lines utilized in this device.
dupsInputFrequency1
The current input line 1 frequency to the UPS system in 1/10 Hz.
dupsInputVoltage1
The Input line 1 voltage of the UPS system in 1/10 V.
dupsInputCurrent1
The Input line 1 current to the UPS system in 1/10 A.
dupsInputFrequency2
The current input line 2 frequency to the UPS system in 1/10 Hz.
dupsInputVoltage2
The Input line 2 voltage of the UPS system in 1/10 V.
dupsInputCurrent2
The Input line 2 current to the UPS system in 1/10 A.
dupsInputFrequency3
The current input line 3 frequency to the UPS system in 1/10 Hz.
dupsInputVoltage3
The Input line 3 voltage of the UPS system in 1/10 V.
dupsInputCurrent3
The Input line 3 current to the UPS system in 1/10 A.
dupsOutputSource
The present source of output power. The enumeration none(7) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.
dupsOutputFrequency
The present output frequency in 1/10 Hz.
dupsOutputNumLines
The number of output lines utilized in this device.
dupsOutputVoltage1
The Output line 1 voltage of the UPS system in 1/10 V.
dupsOutputCurrent1
The Output line 1 current of the UPS system in 1/10 A.
dupsOutputPower1
The Output line 1 real power of the UPS system in watts.
dupsOutputLoad1
The current UPS output line 1 load expressed in percent of rated capacity.
dupsOutputVoltage2
The Output line 2 voltage of the UPS system in 1/10 V.
dupsOutputCurrent2
The Output line 2 current of the UPS system in 1/10 A.
dupsOutputPower2
The Output line 2 real power of the UPS system in watts.
dupsOutputLoad2
The current UPS output line 2 load expressed in percent of rated capacity.
dupsOutputVoltage3
The Output line 3 voltage of the UPS system in 1/10 V.
dupsOutputCurrent3
The Output line 3 current of the UPS system in 1/10 A.
dupsOutputPower3
The Output line 3 real power of the UPS system in watts.
dupsOutputLoad3
The current UPS output line 3 load expressed in percent of rated capacity.
dupsBypassFrequency
The present bypass frequency in 1/10 Hz.
dupsBypassNumLines
The number of bypass lines utilized in this device.
dupsBypassVoltage1
The bypass line 1 voltage of the UPS system in 1/10 V.
dupsBypassCurrent1
The bypass line 1 current of the UPS system in 1/10 A.
dupsBypassPower1
The bypass line 1 real power of the UPS system in watts.
dupsBypassLoad1
The current UPS bypass line 1 load expressed in percent of rated capacity.
dupsBypasstVoltage2
The bypass line 2 voltage of the UPS system in 1/10 V.
dupsBypassCurrent2
The bypass line 2 current of the UPS system in 1/10 A.
dupsBypassPower2
The bypass line 2 real power of the UPS system in watts.
dupsBypassLoad2
The current UPS bypass line 2 load expressed in percent of rated capacity.
dupsBypassVoltage3
The bypass line 3 voltage of the UPS system in 1/10 V.
dupsBypassCurrent3
The bypass line 3 current of the UPS system in 1/10 A.
dupsBypassPower3
The bypass line 3 real power of the UPS system in watts.
dupsBypassLoad3
The current UPS bypass line 3 load expressed in percent of rated capacity.
dupsBatteryCondiction
The indication of the capacity remaining in the UPS system's batteries when AC normal.
dupsBatteryStatus
The indication of the capacity remaining in the UPS system's batteries when AC failed. A value of ok indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of low indicates that the remaining battery run-time is less than o ...
dupsBatteryCharge
dupsSecondsOnBattery
If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.
dupsBatteryEstimatedTime
Estimated time from backup to low battery shutdown.
dupsBatteryVoltage
The magnitude of the present battery voltage in 1/10 V.
dupsBatteryCurrent
The present battery current in 1/10 A.
dupsBatteryCapacity
An estimate of the battery charge remaining expressed as a percent of full charge.
dupsTemperature
The ambient temperature at or near the UPS Battery casing.
dupsTestType
Perform the UPS Test procedure.
dupsTestResultsSummary
The results of the current or last UPS diagnostics test performed. The values for donePass(1), general_test_fail(3), and battery_test_fail(4) indicate that the test completed either successfully, with a warning, or with an error, respectively.Tests which ...
dupsTestResultsDetail
Additional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.
dupsAlarmDisconnect
Does the UPS disconnect?
dupsAlarmPowerFail
Does the input power fail?
dupsAlarmBatteryLow
Are the UPS batteries low?
dupsAlarmLoadWarning
Does the UPS load percent over the load warning value?
dupsAlarmLoadSeverity
Does the UPS load percent over the load severity value?
dupsAlarmLoadOnBypass
Does the UPS load on bypass?
dupsAlarmUPSFault
Does the UPS general fail?
dupsAlarmBatteryGroundFault
Does the UPS battery ground fault?
dupsAlarmTestInProgress
Does the UPS test in progress?
dupsAlarmBatteryTestFail
Does the UPS test fail?
dupsAlarmFuseFailure
Does the UPS fuse failure?
dupsAlarmOutputOverload
Does the UPS output overload?
dupsAlarmOutputOverCurrent
Does the UPS output overcurrent?
dupsAlarmInverterAbnormal
Does the UPS inverter abnormal?
dupsAlarmRectifierAbnormal
Does the UPS rectifier abnormal?
dupsAlarmReserveAbnormal
Does the UPS reserve abnormal?
dupsAlarmLoadOnReserve
Does the UPS load on reserve?
dupsAlarmOverTemperature
Does the UPS over heat?
dupsAlarmOutputBad
Is the UPS output abnormal?
dupsAlarmBypassBad
Is the UPS bypass bad?
dupsAlarmUPSOff
Is the UPS in standby mode?
dupsAlarmChargerFail
Does the UPS charger fail?
dupsAlarmFanFail
Does the UPS fan fail?
dupsAlarmEconomicMode
Indicates whether the UPS is in the economic mode.
dupsAlarmOutputOff
Indicates whether the UPS output is turned off or not.
dupsAlarmSmartShutdown
Indicates whether the Smart Shutdown is in progress.
dupsEnvTemperature
The ambient environmental temperature.
dupsEnvHumidity
The environmental humidity.
dupsEnvSetTemperatureLimit
Alarm dupsAlarmOverTemperature on when the environmental temperature over the value.
dupsEnvSetHumidityLimit
Alarm dupsAlarmOverHumidity on when the environmental humidity over the value.
dupsEnvSetEnvRelay1
dupsEnvSetEnvRelay2
dupsEnvSetEnvRelay3
dupsEnvSetEnvRelay4
dupsAlarmOverEnvTemperature
Does the environment over temperature?
dupsAlarmOverEnvHumidity
Does the environment over humidity?
dupsAlarmEnvRelay1
dupsAlarmEnvRelay2
dupsAlarmEnvRelay3
dupsAlarmEnvRelay4

Download IPHost Network Monitor (500 monitors for 30 days, 50 monitors free forever) to start monitoring network devices right now.

MIBs list