upsShutdownAfterDelay
ups Shutdown After Delay
1.3.6.1.2.1.33.1.8.2
Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) after the indicated number of seconds, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if upsShutdownType = system and the system is already off. Similarly, there is no additional action at that time if upsShutdownType = output and the output is already off. When read, upsShutdownAfterDelay will return the number of seconds remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any upsShutdownAfterDelay already in effect.
Back to rfc1628 MIB page.
IPHost Network monitor uses SNMP for monitoring health and availability of devices and applications in your network. You can send a SNMP Set to any remote device to monitor a specific SNMP object (CPU, Memory, Disk, Server Temperature, RAID failures, IO statistics, connection counts, error and much more).