envRelay2Control

env Relay2 Control
1.3.6.1.4.1.476.1.2.1.1.1.3.2.3

If Control value is 0 then this output may be directly controlled by the SNMP Manager. When Control contains any of the following values, or a value resulting from the sum of any of these values the Agent will activate the output when the any of the associated conditions is sensed and de-activate the output when all conditions clear. DigitalInput1State true(1) 1 DigitalInput2State true(1) 2 DigitalInput3State true(1) 4 DigitalInput4State true(1) 8 DigitalInput5State true(1) 16 DigitalInput6State true(1) 32 DigitalInput7State true(1) 64 DigitalInput8State true(1) 128 DigitalInput9State true(1) 256 DigitalInput10State true(1) 512 Temperature1 above HighLimit 1024 Temperature1 below LowLimit 2048 Temperature2 above HighLimit 4096 Temperature2 below LowLimit 8192 Temperature3 above HighLimit 16384 Temperature3 below LowLimit 32768 Humidity1 above HighLimit 65536 Humidity1 below LowLimit 131072 Humidity2 above HighLimit 262144 Humidity2 below LowLimit 524288 The Control variable is stored in non-volatile memory.

Back to LIEBERT-SITENET-INTEGRATOR-MIB MIB page.

IPHost Network monitor allows you to monitor envRelay2Control on Liebert device via the SNMP protocol. Download IPHost Network Monitor (500 monitors for 30 days, 50 monitors free forever) to start monitoring Liebert uninterruptible power sources right now.