ups2-mib

ups2-mib Download

MIBs list

You can select a variable to monitor using the built-in IPHost MIB browser that provides you with all variables, their current values and descriptions taken from the ups2-mib .

OID list for ups2-mib

upsNumUPSs
The number of UPSs available.
upsIdTable
A list of identification table entries. The number of entries is given by the value of upsNumUPSs.
upsIdEntry
An entry containing objects for a particular UPS.
upsIndex
A unique value which identifies a particular UPS.
upsName
The UPS's name. A maximum of 8 characters may be specified. This object is initialized to the UPS's model name.
upsModelType
The UPS's base model type.
upsFwVersion
The UPS's firmware version.
upsSerialNumber
The UPS's serial number as set at the factory.
upsManufDate
The UPS's date of manufacture in the format mm/dd/yy.
upsBatteryTable
A list of battery table entries. The number of entries is given by the value of upsNumUPSs.
upsBatteryEntry
An entry containing objects for a particular UPS.
upsBatteryCapacity
The UPS's remaining battery capacity expressed as a percent of the fully charged condition. The value of this object is the actual percentage * 10 (that is, to determine the actual percentage, divide the value of this object by 10).
upsBatteryVoltage
The UPS's present battery voltage. The value of this object is the actual voltage * 100 (that is, to determine the actual voltage, divide the value of this object by 100).
upsBatteryTest
This object may be written to initiate testing of the UPS's battery packs. Reading this object will always return a 0.
upsBatteryTestResult
The result of the last battery test performed.
upsRunTimeCalibration
This object may be written to initiate or terminate the test used to calibrate the returned run time value. This test will only run if battery capacity is 100%. Results of this test can be retrieved by upsEstimatedRunTimeRemaining. Valid values for wri ...
upsEstimatedRunTimeRemaining
The UPS's estimated remaining run time in minutes. The UPS may be queried when operating in the on-line, bypass, or on-battery modes of operation. The run time estimate is based on available battery capacity and output load.
upsTransferCause
The reason for the most recent transfer to on-battery operation.
upsBatteryTestTime
The frequency of execution of the UPS's automatic battery test. The test may be run immediately upon startup, upon startup and every 7 days thereafter, upon startup and every 14 days thereafter, or never.
upsLowBatteryWarning
The interval between activation of the UPS's low battery alarm warnings and shutdown of the UPS.
upsInputTable
A list of input table entries. The number of entries is given by the value of upsNumUPSs.
upsInputEntry
An entry containing objects for a particular UPS.
upsInputUtilityVoltage
The UPS's utility voltage version.
upsInputVoltage
The UPS's measured utility input voltage. The value of this object is the actual voltage * 10 (that is, to determine the actual voltage, divide the value of this object by 10).
upsInputFailureSensitivity
The sensitivity of the UPS to rapid changes in utility voltage (e.g., blackouts, spikes, or notches) or abnormal changes in utility frequency.
upsInputMaxVoltage
The UPS's maximum input voltage recorded since this object was last read. The value of this object is the actual voltage * 10 (that is, to determine the actual voltage, divide the value of this object by 10).
upsInputMinVoltage
The UPS's minimum input voltage recorded since this object was last read. The value of this object is the actual voltage * 10 (that is, to determine the actual voltage, divide the value of this object by 10).
upsInputFrequency
The UPS's present internal operating frequency in Hz. The value of this object is the actual frequency * 100 (that is, to determine the actual frequency, divide the value of this object by 100).
upsOutputTable
A list of output table entries. The number of entries is given by the value of upsNumUPSs.
upsOutputEntry
An entry containing objects for a particular UPS.
upsOutputVoltage
The measured UPS output voltage. The value of this object is the actual voltage * 10 (that is, to determine the actual voltage, divide the value of this object by 10).
upsOutputUtilityVoltage
The UPS's current on-battery output voltage setting (valid for 220/230/240 Vac version UPSs only). For other version UPSs, reading this object will always return a 0 and writing this object will have no effect.
upsOutputPower
The UPS's output load represented as a percentage of full rated load in Watts. The value of this object is the actual percentage * 10 (that is, to determine the actual percentage, divide the value of this object by 10).
upsStatusTable
A list of status table entries. The number of entries is given by the value of upsNumUPSs.
upsStatusEntry
An entry containing objects for a particular UPS.
upsStatusOperational
This object contains 8 bits of information about the current operational status of the UPS. The bits are encoded as follows: BIT 7: 1=replace battery condition BIT 6: 1=low battery condition BIT 5: 1=overloaded output condition BIT 4: 1=on-battery mo ...
upsStatusFault
This object contains 8 bits of information about the current fault conditions of the UPS. The bits are encoded as follows: BIT 7: 1=UPS fault - internal temperature has exceeded nominal limits BIT 6: 1=UPS fault - bypass relay (where applicable) malfun ...
upsStatusTemp
The UPS's present internal operating temperature in degrees Fahrenheit. The value of this object is the actual temperature * 10 (that is, to determine the actual temperature, divide the value of this object by 10).
upsConfigTable
A list of configuration table entries. The number of entries is given by the value of upsNumUPSs.
upsConfigEntry
An entry containing objects for a particular UPS.
upsConfigAlarm
The UPS's current audible alarm setting. The alarm may be set to activate immediately upon utility failure and for low battery condition, to activate 30 seconds after utility failure and immediately upon low battery condition, to activate upon low batter ...
upsConfigRestoreDefaults
This object may be written to force the UPS to restore the factory default settings for most of the UPS's customizable parameters. Reading this object will always return a 0.
upsExtMeasTable
A list of external measurement table entries. The number of entries is the number of available UPSs to which External Measurement Units are attached.
upsExtMeasEntry
An entry containing objects for a particular UPS.
upsExtMeasFwVersion
The External Measurement Unit's firmware version letter.
upsExtMeasTemp
The local ambient temperature in degrees Fahrenheit as measured by the External Measurement Unit. The value of this object is the actual temperature * 100 (that is, to determine the actual temperature, divide the value of this object by 100).
upsExtMeasHumidity
The local ambient relative humidity in percent as measured by the External Measurement Unit. The value of this object is the actual humidity * 10 (that is, to determine the actual humidity, divide the value of this object by 10).
upsExtMeasAlarmStatus
This object contains 8 bits of information about the current alarm status of the External Measurement Unit. The bits are encoded as follows: BIT 7: 1=Upper temperature limit exceeded BIT 6: 1=Lower temperature limit exceeded BIT 5: 1=Upper relative hu ...
upsExtMeasMaxTemp
The upper temperature limit at which an alarm will be sent.
upsExtMeasMinTemp
The lower temperature limit at which an alarm will be sent.
upsExtMeasMaxHumidity
The upper humidity limit at which an alarm will be sent.
upsExtMeasMinHumidity
The lower humidity limit at which an alarm will be sent.
upsExtMeasContact1AlarmControl
The alarm enable state for the External Measurement Unit's contact input channel #1. If enabled, an alarm will be sent when contact input channel #1 has changed to abnormal state.
upsExtMeasContact2AlarmControl
The alarm enable state for the External Measurement Unit's contact input channel #2. If enabled, an alarm will be sent when contact input channel #2 has changed to abnormal state.
upsExtMeasContact3AlarmControl
The alarm enable state for the External Measurement Unit's contact input channel #3. If enabled, an alarm will be sent when contact input channel #3 has changed to abnormal state.
upsExtMeasContact4AlarmControl
The alarm enable state for the External Measurement Unit's contact input channel #4. If enabled, an alarm will be sent when contact input channel #4 has changed to abnormal state.
upsExtMeasMaxTempAlarmControl
The alarm enable state for the External Measurement Unit's upper temperature limit. If enabled, an alarm will be sent when the ambient temperature rises above the upper temperature limit.
upsExtMeasMinTempAlarmControl
The alarm enable state for the External Measurement Unit's lower temperature limit. If enabled, an alarm will be sent when the ambient temperature falls below the lower temperature limit.
upsExtMeasMaxHumidityAlarmControl
The alarm enable state for the External Measurement Unit's upper humidity limit. If enabled, an alarm will be sent when the ambient relative humidity rises above the upper humidity limit.
upsExtMeasMinHumidityAlarmControl
The alarm enable state for the External Measurement Unit's lower humidity limit. If enabled, an alarm will be sent when the ambient relative humidity falls below the lower humidity limit.
upsAddlFuncsTable
A list of additional functions table entries. The number of entries is the number of available UPSs which are capable of supporting these additional functions.
upsAddlFuncsEntry
An entry containing objects for a particular UPS.
upsAddlFuncsNumBatteryPacks
The number of battery pack units connected to the UPS.
upsAddlFuncsNumBadBatteryPacks
The number of bad (faulty) battery pack units connected to the UPS.
upsAddlFuncsOutputCurrent
The true rms load current drawn from the UPS. The value of this object is the actual amperage * 100 (that is, to determine the actual amperage, divide the value of this object by 100).
upsAddlFuncsOutputApparentPower
The UPS's output load represented as a percentage of full rated load in Volt-Amps. The value of this object is the actual percentage * 10 (that is, to determine the actual percentage, divide the value of this object by 10).
upsAddlFuncsStatusOperational
This object contains 8 bits of information about the current operational status of the UPS. The bits are encoded as follows: BIT 7: 1=UPS ready to power load upon return of normal line or upon user command BIT 6: 1=UPS ready to power load upon user com ...
upsAddlFuncsStatusFault
This object contains 8 bits of information about the current fault conditions of the UPS. The bits are encoded as follows: BIT 7: reserved for future use BIT 6: reserved for future use BIT 5: reserved for future use BIT 4: 1=UPS fault - DC imbalance, ...
upsAddlFuncsConfigPassword
The password that controls access to the UPS's LCD display. A maximum of 4 characters may be entered.
upsAddlFuncsConfigDisable
This object may be written to immediately shut down the UPS, requiring a manual reset. Reading this object will always return a 0.
upsAddlFuncsConfigBypass
This object may be written to cause the UPS to transfer to or from the bypass mode. Reading this object will always return a 0.

You can start network devices monitoring using free 30-day trial version of IPHost Network Monitor right now. Witn IPHost SNMP monitor you can monitor network performance, audit network usage, detect network faults, or inappropriate access. The IPHost's SNMP monitor can communicate and interact with any SNMP-enabled device.