EES-POWER-MIB

EES-POWER-MIB Download

MIBs list

Emerson Energy Systems (EES) Power MIB

IPHost Network Monitor offer an easy way of SNMP monitoring your Liebert Servers, Routers, Switches, Bridges, Firewalls, Repeaters.

OID list for EES-POWER-MIB

identManufacturer
The name of the equipment manufacturer.
identModel
The manufacturers model designation of the power system.
identControllerFirmwareVersion
The firmware (software) version of the controller.
identName
The name of the power plant. This object should be set by the administrator.
systemStatus
Status of the complete plant (highest alarm). One of (1) unknown - status has not yet been defined (2) normal - there are no activated alarms (3) observation - OA, lowest level of 'abnormal' status (4) warning - A3 (5) minor - MA (6) major - CA, highest l ...
systemVoltage
System voltage, stored as mV, including positive or negative sign. The integer 2147483647 represents invalid value.
systemCurrent
System current, stored as mA, including positive or negative sign. The integer 2147483647 represents invalid value.
systemUsedCapacity
Used capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value.
psBatteryVoltage
Battery voltage, stored as mV, including positive or negative sign. The integer 2147483647 represents invalid value.
psBatteryCurrent
Battery current, stored as mA, including positive or negative sign. The integer 2147483647 represents invalid value.
psInputLineAVoltage
The AC line A voltage, stored as mV. The integer 2147483647 represents invalid value.
psInputLineBVoltage
The AC line B voltage, stored as mV. The integer 2147483647 represents invalid value.
psInputLineCVoltage
The AC line C voltage, stored as mV. The integer 2147483647 represents invalid value.
psTemperature1
The first route temperature, stored as 0.001 Celsius degree. The integer 2147483647 represents invalid value.
psTemperature2
The second route temperature, stored as 0.001 Celsius degree. The integer 2147483647 represents invalid value..
psStatusCommunication
The status of communication with the Power System. interrupt(3) indicates some errors occurred between Power System and agent.
psStatusBatteryMode
The status of battery modes, FloatCharging(2), ShortTest(3), BoostChargingForTest(4), ManualTesting(5), PlanTesting(6), ACFailTesting(7), ACFail(8), ManualBoostCharging(9), AutoBoostCharging(10), CyclicBoostCharging(11), MasterBoostCharging(12), MasterBat ...
psSMACNumber
The number of SM AC module.
psSMBATNumber
The number of SM BAT module.
psSMIONumber
The number of SM IO module.
alarmLastTrapNo
The sequence number of last submitted alarm trap, also last row in alarmTrapTable.
alarmTrapTable
Table holding information about the submitted alarm traps.
alarmTrapEntry
An entry (conceptual row) in the alarmTrapTable.
alarmTrapNo
The unique sequence number of this alarm trap.
alarmTime
Date and time when event occured (local time), including timezone if supported by controller.
alarmStatusChange
The type of alarm change. One of (1) activated (2) deactivated
alarmSeverity
The severity of the alarm. One of (3) observation - OA, lowest level of alarm severity (4) warning - A3 (5) minor - MA (6) major - CA, highest level of alarm severity
alarmDescription
Free-text description of alarm.
alarmType
Alarm type, i.e. an integer specifying the type of alarm.