LIEBERT-SERIES-4300-UPS-MIB

LIEBERT-SERIES-4300-UPS-MIB Download

MIBs list

This MIB defines objects for the Liebert AP4300 SNMP Agents.

IPHost Network Monitor offer an easy way of SNMP monitoring your Liebert Servers, Routers, Switches, Bridges, Firewalls, Repeaters.

OID list for LIEBERT-SERIES-4300-UPS-MIB

lcUpsIdentManufacturer
The UPS manufacturer.
lcUpsIdentModel
The UPS Model designation.
lcUpsIdentSoftwareVersion
The UPS SNMP Agent software version.
lcUpsIdentSpecific
A reference to MIB definitions specific to the particular UPS being managed. This object is used to locate the product-specific MIB for this device. If this information is not present, its value should be the OBJECT IDENTIFIER { 0 0 }, which is a syntacti ...
lcUpsBatTimeRemaining
The estimated time to depletion of battery charge. (Unit of measure: Minute)
lcUpsBatTemperature
The battery temperature. (Unit of measure: Degree, Centigrade)
lcUpsBatVoltage
The current battery voltage. (Unit of measure: volt)
lcUpsBatCapacity
The current battery capacity in percentage of total available.
lcUpsOutputFrequency
The current output frequency. (Unit of measure: Hertz)
lcUpsOutputLoad
The current output load percentage.
lcUpsOutputNumLines
The number of output lines utilized in this device. This entry indicates the number of rows in the output table.
lcUpsOutputTable
lcUpsOutputEntry
lcUpsOutputLine
The output Line.
lcUpsOutputVoltage
The output voltage. (Unit of measure: Volt)
lcUpsOutputCurrent
The output current. (Unit of measure: Amp)
lcUpsOutputVA
The output volt-amps.
lcUpsOutputWatts
The output power in watts.
lcUpsInverterStatus
The state of the inverter. Unknown is returned if the state can not be determined.
lcUpsInverterTemp
The temperature of the inverter. (Unit of measure: degree, Centigrade)
lcUpsAlarms
The current number of alarm conditions.
lcUpsAlarmTable
lcUpsAlarmEntry
lcUpsAlarmId
A unique identifier for an alarm condition. This value must remain constant between agent initializations.
lcUpsAlarmDescr
A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.
lcUpsAlarmTime
The value of sysUpTime when the alarm condition occured.
lcUpsTestBattery
Setting this variable to 'start' will initiate the battery test. Setting this variable to 'abort' will stop the battery test if the test is in- progress, otherwise it has no effect. Setting this variable to 'unknown' has no effect. Reading this variable ...
lcUpsTestBatteryStatus
The status of the battery test.
lcUpsTestDiag
Setting this variable to 'start' will initiate the diagnostics test. Setting this variable to 'abort' will stop the diagnostics test if the test is in-progress, otherwise it has no effect. Setting this variable to 'unknown' has no effect. Reading this v ...
lcUpsTestDiagStatus
The status of the diagnostics test.
lcUpsControlOutputOffDelay
Setting this object causes the agent to instruct the UPS to turn off the output after the indicated number of seconds. The agent counts down the number of seconds until the event will take place. The agent issues an lcUpsOutputOffTrap when the countdown ...
lcUpsControlOutputOnDelay
Setting this object causes the agent to instruct the UPS to turn on the output after the indicated number of seconds. The agent counts down the number of seconds until the event will take place. The agent issues an lcUpsOutputOnTrap when the countdown f ...
lcUpsControlOutputOffTrapDelay
When 'lcUpsControlOutputOffDelay' reaches a value less than or equal to this object's value, an lcUpsOutputOffWarningTrap will be produced and this object will be reset to 0.
lcUpsControlOutputOnTrapDelay
When 'lcUpsControlOutputOnDelay' reaches a value less than or equal to this object's value, an lcUpsOutputOnWarningTrap will be produced and this object will be reset to 0.
lcUpsControlUnixShutdownDelay
Setting this object causes the agent to instruct the UPS to perform a UNIX Shutdown in the indicated number of seconds. The agent counts down the number of seconds until the event will take place. A Unix shutdown is only valid if the UPS is on Battery. ...
lcUpsControlUnixShutdownTrapDelay
When 'lcUpsControlUnixShutdownDelay' reaches a value less than or equal to this object's value, an lcUpsUnixShutdownWarningTrap will be produced and this object will be reset to 0.
lcUpsControlCancelCommands
Setting this variable to 'cancel' will cause the agent to issue instructions to the UPS to cancel all outstanding commands, such as lcUpsControlOutputOff, lcUpsControlOutputOn, lcUpsControlUnixShutdown.
lcUpsControlRebootAgentDelay
Setting this object causes the agent to reboot after the indicated number of seconds have expired. The value will count down until the event takes place. The command can be cancelled by setting lcUpsControlCancleCommand to the value cancel.
lcUpsNominalOutputVoltage
The nominal output voltage. (Unit of measure: volt)
lcUpsNominalInputVoltage
The nominal input voltage. (Unit of measure: volt)
lcUpsNominalOutputVA
The nominal Volt-Amp rating.
lcUpsNominalOutputFreq
The nominal output frequency. (Unit of measure: Hertz)
lcUpsNominalInputFreq
The nominal input frequency. (Unit of measure: Hertz)
ls43cUpsIdentFirmwareVersion
The firmware revision level of the UPS.
ls43cUpsConfigBypassInstalled
Indicates if a bypass is installed in the UPS.
ls43cUpsOnBypass
Indicates that the UPS is currently on bypass.
ls43cUpsBypassFrequency
The current bypass frequency. (Unit of measure: Hertz)
ls43cUpsBypassNumLines
The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.
ls43cUpsBypassTable
ls43cUpsBypassEntry
ls43cUpsBypassLine
The bypass Line.
ls43cUpsBypassVoltage
The bypass voltage. (Unit of measure: Volt)
ls43cUpsBypassCurrent
The bypass current. (Unit of measure: Amp)