LIEBERT-SERIES-600-UPS-CONTROL-CABINET-MIB

LIEBERT-SERIES-600-UPS-CONTROL-CABINET-MIB Download

MIBs list

This MIB defines objects for the Liebert AP600 Control Cabinet SNMP Agents.

IPHost Network Monitor offer an easy way of SNMP monitoring your Liebert Servers, Routers, Switches, Bridges, Firewalls, Repeaters.

OID list for LIEBERT-SERIES-600-UPS-CONTROL-CABINET-MIB

lcUpsIdentManufacturer
The UPS manufacturer.
lcUpsIdentModel
The UPS Model designation.
lcUpsIdentSoftwareVersion
The UPS SNMP Agent software version.
lcUpsIdentSpecific
A reference to MIB definitions specific to the particular UPS being managed. This object is used to locate the product-specific MIB for this device. If this information is not present, its value should be the OBJECT IDENTIFIER { 0 0 }, which is a syntacti ...
lcUpsIdentFirmwareVersion
The firmware revision level of the UPS.
lcUpsIdentSerialNumber
The serial number of the UPS.
lcUpsInputNumLines
The number of input lines utilized in this device. This entry indicates the number of rows in the input table.
lcUpsInputTable
lcUpsInputEntry
lcUpsInputLine
The input Line.
lcUpsInputVoltage
The input voltage. (Unit of measure: Volt)
lcUpsOutputFrequency
The current output frequency. (Unit of measure: Hertz)
lcUpsOutputLoad
The current output load percentage.
lcUpsOutputNumLines
The number of output lines utilized in this device. This entry indicates the number of rows in the output table.
lcUpsOutputTable
lcUpsOutputEntry
lcUpsOutputLine
The output Line.
lcUpsOutputVoltage
The output voltage. (Unit of measure: Volt)
lcUpsOutputCurrent
The output current. (Unit of measure: Amp)
lcUpsOutputWatts
The output power in watts.
lcUpsAlarms
The current number of alarm conditions.
lcUpsAlarmTable
lcUpsAlarmEntry
lcUpsAlarmId
A unique identifier for an alarm condition. This value must remain constant between agent initializations.
lcUpsAlarmDescr
A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.
lcUpsAlarmTime
The value of sysUpTime when the alarm condition occured.
lcUpsControlRebootAgentDelay
Setting this object causes the agent to reboot after the indicated number of seconds have expired. The value will count down until the event takes place.
lcUpsNominalOutputVoltage
The nominal output voltage. (Unit of measure: volt)
lcUpsNominalInputVoltage
The nominal input voltage. (Unit of measure: volt)
lcUpsNominalOutputFreq
The nominal output frequency. (Unit of measure: Hertz)
lcUpsNominalOutputVaRating
The nominal Volt-Amp rating.
lcUpsNominalOutputWattsRating
The nominal power rating. (Unit of measure: watt)
lcUpsOnBypass
Indicates that the UPS is currently on bypass.
lcUpsBypassFrequency
The current bypass frequency. (Unit of measure: Hertz)
lcUpsBypassNumLines
The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.
lcUpsBypassTable
lcUpsBypassEntry
lcUpsBypassLine
The bypass Line.
lcUpsBypassVoltage
The bypass voltage. (Unit of measure: Volt)
lcUpsBypassCurrent
The bypass current. (Unit of measure: Amp)
lcUpsConfigType
Indicates the UPS topology.
lcUpsConfigBypassInstalled
Indicates if a bypass is installed in the UPS.
lcUpsConfigModuleCount
A number identifying how many multi-module UPS are connected to the System Control Cabinet.
lcUpsConfigCurrentModule
A number identifying which module of a multi-module UPS is currently being monitored.