LIEBERT-UPS-MIB

LIEBERT-UPS-MIB Download

MIBs list

This MIB defines objects for all Liebert UPS SNMP Agents

IPHost Network Monitor offer an easy way of SNMP monitoring your Liebert Servers, Routers, Switches, Bridges, Firewalls, Repeaters.

OID list for LIEBERT-UPS-MIB

lcUpsIdentManufacturer
The UPS manufacturer.
lcUpsIdentModel
The UPS Model designation.
lcUpsIdentSoftwareVersion
The UPS SNMP Agent software version.
lcUpsIdentSpecific
A reference to MIB definitions specific to the particular UPS being managed. This object is used to locate the product-specific MIB for this device. If this information is not present, its value should be the OBJECT IDENTIFIER { 0 0 }, which is a syntacti ...
lcUpsIdentFirmwareVersion
The firmware revision level of the UPS.
lcUpsIdentSerialNumber
The serial number of the UPS.
lcUpsIdentManufactureDate
The date of manufacture of the UPS.
lcUpsBatTimeRemaining
The estimated time to depletion of battery charge. (Unit of measure: Minute)
lcUpsBatTemperature
The battery temperature. (Unit of measure: Degree, Centigrade)
lcUpsBatVoltage
The current battery voltage. (Unit of measure: volt)
lcUpsBatCurrent
The current battery discharging/charging current. (Unit of measure: Amp)
lcUpsBatCapacity
The current battery capacity in percentage of total available.
lcUpsBatTotalDischCounts
The number of discharges the UPS has experienced.
lcUpsBatCycleDurationInSeconds
The total accumulated discharge time in seconds.
lcUpsBatAmpHours
The number of amp hours withdrawn from battery.
lcUpsBatKWhours
The number of Kilowatt-hours withdrawn from battery.
lcUpsBatWattHours
The number of Watt-hours withdrawn from battery.
lcUpsInputFrequency
The current input frequency. (Unit of measure: Hertz)
lcUpsInputBrownOuts
The number of brown-out conditions the UPS has experienced.
lcUpsInputBlackOuts
The number of black-out conditions the UPS has experienced.
lcUpsInputTransients
The number of transient (surge and spike) conditions the UPS has experienced.
lcUpsInputNumLines
The number of input lines utilized in this device. This entry indicates the number of rows in the input table.
lcUpsInputTable
lcUpsInputEntry
lcUpsInputLine
The input Line.
lcUpsInputVoltage
The input voltage. (Unit of measure: Volt)
lcUpsInputCurrent
The input current. (Unit of measure: Amp)
lcUpsInputVA
The input volt-amps.
lcUpsOutputFrequency
The current output frequency. (Unit of measure: Hertz)
lcUpsOutputLoad
The current output load percentage.
lcUpsOutputNumLines
The number of output lines utilized in this device. This entry indicates the number of rows in the output table.
lcUpsOutputTable
lcUpsOutputEntry
lcUpsOutputLine
The output Line.
lcUpsOutputVoltage
The output voltage. (Unit of measure: Volt)
lcUpsOutputCurrent
The output current. (Unit of measure: Amp)
lcUpsOutputVA
The output volt-amps.
lcUpsOutputWatts
The output power in watts.
lcUpsInverterStatus
The state of the inverter. Unknown is returned if the state can not be determined.
lcUpsInverterTemp
The temperature of the inverter. (Unit of measure: degree, Centigrade)
lcUpsAlarms
The current number of alarm conditions.
lcUpsAlarmTable
lcUpsAlarmEntry
lcUpsAlarmId
A unique identifier for an alarm condition. This value must remain constant between agent initializations.
lcUpsAlarmDescr
A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.
lcUpsAlarmTime
The value of sysUpTime when the alarm condition occured.
lcUpsTestBattery
Setting this variable to 'start' will initiate the battery test. Setting this variable to 'abort' will stop the battery test if the test is in- progress, otherwise it has no effect. Setting this variable to 'unknown' has no effect. Reading this variable ...
lcUpsTestBatteryStatus
The status of the battery test.
lcUpsTestDiag
Setting this variable to 'start' will initiate the diagnostics test. Setting this variable to 'abort' will stop the diagnostics test if the test is in-progress, otherwise it has no effect. Setting this variable to 'unknown' has no effect. Reading this v ...
lcUpsTestDiagStatus
The status of the diagnostics test.
lcUpsControlOutputOffDelay
Setting this object causes the agent to instruct the UPS to turn off the output after the indicated number of seconds. The agent counts down the number of seconds until the event will take place. The agent issues an lcUpsOutputOffTrap when the countdown ...
lcUpsControlOutputOnDelay
Setting this object causes the agent to instruct the UPS to turn on the output after the indicated number of seconds. The agent counts down the number of seconds until the event will take place. The agent issues an lcUpsOutputOnTrap when the countdown f ...
lcUpsControlOutputOffTrapDelay
When 'lcUpsControlOutputOffDelay' reaches a value less than or equal to this object's value, an lcUpsOutputOffWarningTrap will be produced and this object will be reset to 0.
lcUpsControlOutputOnTrapDelay
When 'lcUpsControlOutputOnDelay' reaches a value less than or equal to this object's value, an lcUpsOutputOnWarningTrap will be produced and this object will be reset to 0.
lcUpsControlUnixShutdownDelay
Setting this object causes the agent to instruct the UPS to perform a UNIX Shutdown in the indicated number of seconds. The agent counts down the number of seconds until the event will take place. A Unix shutdown is only valid if the UPS is on Battery. ...
lcUpsControlUnixShutdownTrapDelay
When 'lcUpsControlUnixShutdownDelay' reaches a value less than or equal to this object's value, an lcUpsUnixShutdownWarningTrap will be produced and this object will be reset to 0.
lcUpsControlCancelCommands
Setting this variable to 'cancel' will cause the agent to issue instructions to the UPS to cancel all outstanding commands, such as lcUpsControlOutputOff, lcUpsControlOutputOn, lcUpsControlUnixShutdown.
lcUpsControlRebootAgentDelay
Setting this object causes the agent to reboot after the indicated number of seconds have expired. The value will count down until the event takes place.
lcUpsNominalOutputVoltage
The nominal output voltage. (Unit of measure: volt)
lcUpsNominalInputVoltage
The nominal input voltage. (Unit of measure: volt)
lcUpsNominalOutputVA
The nominal Volt-Amp rating.
lcUpsNominalOutputWatts
The nominal power rating. (Unit of measure: watt)
lcUpsNominalOutputFreq
The nominal output frequency. (Unit of measure: Hertz)
lcUpsNominalInputFreq
The nominal input frequency. (Unit of measure: Hertz)
lcUpsNominalOutputVaRating
The nominal Volt-Amp rating.
lcUpsNominalOutputWattsRating
The nominal power rating. (Unit of measure: watt)
lcUpsOnBypass
Indicates that the UPS is currently on bypass.
lcUpsBypassFrequency
The current bypass frequency. (Unit of measure: Hertz)
lcUpsBypassNumLines
The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.
lcUpsBypassTable
lcUpsBypassEntry
lcUpsBypassLine
The bypass Line.
lcUpsBypassVoltage
The bypass voltage. (Unit of measure: Volt)
lcUpsBypassCurrent
The bypass current. (Unit of measure: Amp)
lcUpsConfigType
Indicates the UPS topology.
lcUpsConfigBypassInstalled
Indicates if a bypass is installed in the UPS.
lcUpsConfigModuleCount
A number identifying how many multi-module UPS are connected to the System Control Cabinet.
lcUpsConfigCurrentModule
A number identifying which module of a multi-module UPS is currently being monitored.
lcUpsConfigAudibleStatus
The requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this object to muted(3) when the audible alarm is sounding shall temporarily silence the alarm.
lcUpsConfigLowBattTime
The value of lcUpsBatTimeRemaining at which a lowBatteryWarning condition is declared. (Unit of measure: Minute)
lcUpsConfigAutoRestart
Setting this object will start the output after the indicated number of ticks (1 tick = 10 seconds), including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will disable au ...
lcUpsSwitchedReceptMaxNum
The maximum number of switched receptacles supported by the Ups.
lcUpsSwitchedReceptTable
lcUpsSwitchedReceptEntry
lcUpsSwitchedReceptIndex
lcUpsSwitchedReceptOnDelay
Setting this object causes the agent to instruct the UPS to turn on a receptacle after the indicated number of seconds. The agent counts down the number of seconds until the event will take place. The agent issues an lcUpsReceptOnTrap when the countdown ...
lcUpsSwitchedReceptOnTrapDelay
When 'lcUpsSwitchedReceptOnDelay' reaches a value less than or equal to this object's value, an lcUpsReceptOnWarningTrap will be produced and this object will be reset to 0.
lcUpsSwitchedReceptOffDelay
Setting this object causes the agent to instruct the UPS to turn off a receptacle after the indicated number of seconds. The agent counts down the number of seconds until the event will take place. The agent issues an lcUpsReceptOffTrap when the countdo ...
lcUpsSwitchedReceptOffTrapDelay
When 'lcUpsSwitchedReceptOffDelay' reaches a value less than or equal to this object's value, an lcUpsReceptOffWarningTrap will be produced and this object will be reset to 0.
lcUpsSwitchedReceptStatus
The status of the device receptacle. Note that some devices may support Switched of device receptacles as a group only (by using lcUpsSwitchedOutputOffDelay and lcUpsSwitchedOutputOnDelay).
lcUpsSwitchedReceptLabel
A user-defined text string associated with a switched receptacle. This may be used to describe the load powered from the receptacle. The text string is stored in non-volatile memory.
lsUpsIdentFirmwareVersion
The firmware revision level of the UPS.
lsUpsConfigBypassInstalled
Indicates if a bypass is installed in the UPS.
lsUpsOnBypass
Indicates that the UPS is currently on bypass.
lsUpsBypassFrequency
The current bypass frequency. (Unit of measure: Hertz)
lsUpsBypassNumLines
The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.
lsUpsBypassTable
lsUpsBypassEntry
lsUpsBypassLine
The bypass Line.
lsUpsBypassVoltage
The bypass voltage. (Unit of measure: Volt)
lsUpsBypassCurrent
The bypass current. (Unit of measure: Amp)
ldUpsInputMaxVoltsSinceLastPoll
The maximum input voltage encountered since the object was last retrieved. Note: if there are multiple managers talking to the same agent, the use of this object needs to be coordinated.
ldUpsInputMinVoltsSinceLastPoll
The minimum input voltage encountered since the object was last retrieved. Note: if there are multiple managers talking to the same agent, the use of this object needs to be coordinated.
ldUpsOutputMaxVoltsSinceLastPoll
The maximum output voltage encountered since the object was last retrieved. Note: if there are multiple managers talking to the same agent, the use of this object needs to be coordinated.
ldUpsOutputMinVoltsSinceLastPoll
The minimum output voltage encountered since the object was last retrieved. Note: if there are multiple managers talking to the same agent, the use of this object needs to be coordinated.
luSeries200InputMaxVoltsSinceLastPoll
The maximum input voltage encountered since the object was last retrieved. Note: if there are multiple managers talking to the same agent, the use of this object needs to be coordinated.
luSeries200InputMinVoltsSinceLastPoll
The minimum input voltage encountered since the object was last retrieved. Note: if there are multiple managers talking to the same agent, the use of this object needs to be coordinated.
luSeries200ConfigBypassInstalled
Indicates if a bypass is installed in the UPS.
luSeries200ConfigFrequencyChangerModel
Indicates whether this AP200 model is a frequency changer model.
luSeries200OnBypass
Indicates that the UPS is currently on bypass.
ls43cUpsIdentFirmwareVersion
The firmware revision level of the UPS.
ls43cUpsConfigBypassInstalled
Indicates if a bypass is installed in the UPS.
ls43cUpsOnBypass
Indicates that the UPS is currently on bypass.
ls43cUpsBypassFrequency
The current bypass frequency. (Unit of measure: Hertz)
ls43cUpsBypassNumLines
The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.
ls43cUpsBypassTable
ls43cUpsBypassEntry
ls43cUpsBypassLine
The bypass Line.
ls43cUpsBypassVoltage
The bypass voltage. (Unit of measure: Volt)
ls43cUpsBypassCurrent
The bypass current. (Unit of measure: Amp)

Download IPHost Network Monitor (500 monitors for 30 days, 50 monitors free forever) to start monitoring network devices right now.