XUPS-MIB

XUPS-MIB Download

MIBs list

IPHost Network Monitor offer an easy way of SNMP monitoring your Eaton Servers, Routers, Switches, Bridges, Firewalls, Repeaters.

OID list for XUPS-MIB

xupsIdentManufacturer
The UPS Manufacturer Name (e.g. Eaton Corporation).
xupsIdentModel
The UPS Model (e.g. Powerware Plus Model 18).
xupsIdentSoftwareVersion
The firmware revision level(s) of the UPS microcontroller(s).
xupsIdentOemCode
A binary code indicating who the UPS was manufactured or labeled for. 0 or 255 indicates Eaton itself.
xupsBatTimeRemaining
Battery run time in seconds before UPS turns off due to low battery.
xupsBatVoltage
Battery voltage as reported by the UPS meters.
xupsBatCurrent
Battery Current as reported by the UPS metering. Current is positive when discharging, negative when recharging the battery.
xupsBatCapacity
Battery percent charge.
xupsBatteryAbmStatus
Gives the status of the Advanced Battery Management; batteryFloating(3) status means that the charger is temporarily charging the battery to its float voltage; batteryResting(4) is the state when the battery is fully charged and none of the other actions ...
xupsBatteryLastReplacedDate
The date when the Batteries in this UPS were last replaced. Should be the same as xupsConfigInstallDate initially. Free text format, so the preferred local date format may be used (MM/DD/YYYY, DD-Mon-YYYY, etc).
xupsInputFrequency
The utility line frequency in tenths of Hz.
xupsInputLineBads
The number of times the Input was out of tolerance in voltage or frequency.
xupsInputNumPhases
The number of input phases (normally 1 to 3).
xupsInputTable
A list of input table entries. The number of entries is given by the value of xupsInputNumPhases.
xupsInputEntry
The input table entry containing the current, voltage, etc. readings for one phase.
xupsInputPhase
The number of the phase. Serves as index for input table.
xupsInputVoltage
The measured input voltage from the UPS meters in volts.
xupsInputCurrent
The measured input current from the UPS meters in amps.
xupsInputWatts
The measured input real power in watts.
xupsInputSource
The present external source of input power. The enumeration none(2) indicates that there is no external source of power, for example, the UPS is On Battery (an internal source). The bypassFeed(4) can only be used when the Bypass source is known to be a s ...
xupsDualInputStatus
The present status of the sources of input power in a dual source UPS. The enumeration primarySourceGood(2) indicates that the primary source of power is present and within 'normal' ranges for voltage and frequency, but the secondary source is either not ...
xupsSecondaryInputWatch
This object enables(2) or disables(1) the alarms and traps related to the availability and use of the secondary input of a dual-input UPS (i.e., OnAlternatePowerSource and AltPowerNotAvailable). To avoid nuisance alarms and traps, this object should be se ...
xupsOutputLoad
The UPS output load in percent of rated capacity.
xupsOutputFrequency
The measured UPS output frequency in tenths of Hz.
xupsOutputNumPhases
The number of metered output phases.
xupsOutputTable
A list of output table entries. The number of entries is given by the value of xupsOutputNumPhases.
xupsOutputEntry
Output Table Entry containing voltage, current, etc.
xupsOutputPhase
The number {1..3} of the output phase.
xupsOutputVoltage
The measured output voltage from the UPS metering in volts.
xupsOutputCurrent
The measured UPS output current in amps.
xupsOutputWatts
The measured real output power in watts.
xupsOutputSource
The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.
xupsBypassFrequency
The bypass frequency in tenths of Hz.
xupsBypassNumPhases
The number of lines in the UPS bypass table.
xupsBypassTable
A list of bypass table entries. The number of entries is given by the value of xupsBypassNumPhases.
xupsBypassEntry
Bypass Table Entry containing voltage for each phase.
xupsBypassPhase
The Bypass Phase, index for the table.
xupsBypassVoltage
The measured UPS bypass voltage in volts.
xupsEnvAmbientTemp
The reading of the ambient temperature in the vicinity of the UPS or SNMP agent.
xupsEnvAmbientLowerLimit
The Lower Limit of the ambient temperature; if xupsEnvAmbientTemp falls below this value, the xupsAmbientTempBad alarm will occur.
xupsEnvAmbientUpperLimit
The Upper Limit of the ambient temperature; if xupsEnvAmbientTemp rises above this value, the xupsAmbientTempBad alarm will occur. This value should be greater than xupsEnvAmbientLowerLimit.
xupsEnvAmbientHumidity
The reading of the ambient humidity in the vicinity of the UPS or SNMP agent.
xupsAlarms
The current number of alarm conditions.
xupsAlarmTable
A list of alarm table entries. The number of entries is given by the value of xupsAlarms. Note that this table is sparsely (non-consecutively) numbered and will be empty if there are no active alarms.
xupsAlarmEntry
Alarm Table Entry containing descriptive information for one alarm entry.
xupsAlarmID
A unique identifier for an alarm condition.
xupsAlarmDescr
A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.
xupsAlarmTime
The value of the MIB-II variable sysUpTime when the alarm condition occurred.
xupsAlarmNumEvents
The number of entries in the UPS event history queue.
xupsAlarmEventTable
A table of the UPS internal event history queue.
xupsAlarmEventEntry
One of the entries in the UPS event history queue.
xupsAlarmEventID
A unique number that reflects the order in which the event occurred. The oldest event in the queue will be number 1. Subsequent events will be numbered 2, 3, 4, etc.
xupsAlarmEventDateAndTime
The time and date that an event occurred as recorded in the UPS internal event queue. This string will reflect the time and date as set in the UPS itself and will not be referenced to sysUpTime. The format is MM/DD/YYYY:HH:MM:SS. Time is 24 hour standar ...
xupsAlarmEventKind
Enumerated value that tells whether the event is an occurrence of an alarm condition or a clearing of an alarm condition.
xupsAlarmEventDescr
A description of the event stored in the UPS event queue. This description will be a sixteen bit integer value representing one of the defined alarms in the Powerware Binary Computer Mode communication specification; for example, a value of 0 represents t ...
xupsAlarmEventMsg
A text string describing each entry in the Event Log. The format of this text message is free (not fixed) for the operator to read; good contents would be a time & date stamp, the event type, and a description of the event.
xupsTestStart
Setting this object initiates the requested Test. If a UPS does not support the requested test, the set operation may succeed but the result will end up as notSupported. When read, this object indicates the last test requested via this object, if any. Cur ...
xupsTestBatteryStatus
Reading this enumerated value gives an indication of the (last) UPS Battery test status.
xupsLastGeneralTest
Indicates the last UPS test requested via xupsTestStart or by other non-SNMP means, other than for the testBattery (1) case. The results of the test indicated by this object are reported in xupsLastGeneralTestResult.
xupsLastGeneralTestResult
Reading this enumerated value gives the result of the test indicated in xupsLastGeneralTest.
xupsControlOutputOffDelay
Setting this value to other than zero will cause the UPS output to turn off after the number of seconds. Setting it to 0 will cause an attempt to abort a pending shutdown.
xupsControlOutputOnDelay
Setting this value to other than zero will cause the UPS output to turn on after the number of seconds. Setting it to 0 will cause an attempt to abort a pending startup.
xupsControlOutputOffTrapDelay
When xupsControlOutputOffDelay reaches this value, a trap will be sent.
xupsControlOutputOnTrapDelay
When xupsControlOutputOnDelay reaches this value, a xupsOutputOff trap will be sent.
xupsControlToBypassDelay
Setting this value to other than zero will cause the UPS output to go to Bypass after the number of seconds. If the Bypass is unavailable, this may cause the UPS to not supply power to the load. Setting it to 0 will cause an attempt to abort a pending shu ...
xupsLoadShedSecsWithRestart
Setting this value will cause the UPS output to turn off after the set number of seconds, then restart (after a UPS-defined 'down time') when the utility is again available. Unlike xupsControlOutputOffDelay, which might or might not, this object always ma ...
xupsConfigOutputVoltage
The nominal UPS Output voltage per phase in volts.
xupsConfigInputVoltage
The nominal UPS Input voltage per phase in volts.
xupsConfigOutputWatts
The nominal UPS available real power output in watts.
xupsConfigOutputFreq
The nominal output frequency in tenths of Hz.
xupsConfigDateAndTime
Date and time information for the UPS. Setting this variable will initiate a set UPS date and time to this value. Reading this variable will return the UPS time and date. This value is not referenced to sysUpTime. It is simply the clock value from the ...
xupsConfigLowOutputVoltageLimit
The Lower limit for acceptable Output Voltage, per the UPS specifications.
xupsConfigHighOutputVoltageLimit
The Upper limit for acceptable Output Voltage, per the UPS specifications.
xupsConfigInstallDate
The date when this UPS was installed. Free text format, so the preferred local date format may be used (MM/DD/YYYY, DD-Mon-YYYY, etc).
xupsMaxTrapLevel
The level of severity of traps which will be sent to the requesting host; individual trap receivers will have individual values for this variable. Values are: (1) none: no traps will be sent to this host; (2) critical: only traps for Critical alarm condi ...
xupsSendTrapType
The type of traps which will be sent to the requesting host; individual trap receivers will have individual values for this variable. The additional variables in types (3) and (4) are useful for determining which UPS is the source on multi-port network a ...
xupsTrapMessage
A descriptive text message which may be sent with traps to further explain the reason for the trap. This object is not-accessible to MIB browsers, but had to be changed to read-only to satisfy SMIv2 syntax checkers since it is included in traps.
xupsHeartbeatMinsInterval
How often to send the xupstdHeartbeat trap, in units of minutes. A setting of 0 disables the Heartbeat function.
xupsNumReceptacles
The number of independently controllable Receptacles, as described in the xupsRecepTable.
xupsRecepTable
A list of receptacle table entries. The number of entries is given by the value of xupsNumReceptacles.
xupsRecepEntry
A receptacle table entry containing the status and control values for one receptacle.
xupsRecepIndex
The number of the Receptacle. Serves as index for Receptacle table.
xupsRecepStatus
The Recep Status 1=On/Close, 2=Off/Open, 3=On w/Pending Off, 4=Off w/Pending ON, 5=Unknown, 6=Reserved for future, 7=Failed in Closed position, 8=Failed in Open position.
xupsRecepOffDelaySecs
The Delay until the Receptacle is turned Off. Setting this value to other than -1 will cause the UPS output to turn off after the number of seconds (0 is immediately). Setting it to -1 will cause an attempt to abort a pending shutdown. When this object i ...
xupsRecepOnDelaySecs
The Delay until the Receptacle is turned On. Setting this value to other than -1 will cause the UPS output to turn on after the number of seconds (0 is immediately). Setting it to -1 will cause an attempt to abort a pending restart.
xupsRecepAutoOffDelay
The delay after going On Battery until the Receptacle is automatically turned Off. A value of -1 means that this Output should never be turned Off automatically, but must be turned Off only by command. Values from 0 to 30 are valid, but probably innappro ...
xupsRecepAutoOnDelay
Seconds delay after the Outlet is signaled to turn On before the Output is Automatically turned ON. A value of -1 means that this Output should never be turned On automatically, but only when specifically commanded to do so. A value of 0 means that the Re ...
xupsRecepShedSecsWithRestart
Setting this value will cause the UPS output to turn off after the set number of seconds, then restart (after a UPS-defined 'down time') when the utility is again available. Unlike xupsRecepOffDelaySecs, which might or might not, this object always maps t ...
xupsTopologyType
Value which denotes the type of UPS by its power topology. Values are the same as those described in the XCP Topology block's Overall Topology field.
xupsTopoMachineCode
ID Value which denotes the Powerware model of the UPS for software. Values are the same as those described in the XCP Configuration block's Machine Code field.
xupsTopoUnitNumber
Identifies which unit and what type of data is being reported. A value of 0 means that this MIB information comes from the top-level system view (eg, manifold module or system bypass cabinet reporting total system output). Standalone units also use a val ...
xupsTopoPowerStrategy
Value which denotes which Power Strategy is currently set for the UPS. The values are: highAlert(1) - The UPS shall optimize its operating state to maximize its power-protection levels. This mode will be held for at most 24 hours. standard(2) - Balanced, ...
xupsIdentFullGroup
The Full set of xupsIdent subgroup objects.
xupsBatteryFullGroup
The Full set of xupsBattery subgroup objects.
xupsInputFullGroup
The Full set of xupsInput subgroup objects.
xupsInputTableFullGroup
The Full set of xupsInputTable subgroup objects.
xupsOutputFullGroup
The Full set of xupsOutput subgroup objects.
xupsOutputTableFullGroup
The Full set of xupsOutputTable subgroup objects.
xupsBypassFullGroup
The Full set of xupsBypass subgroup objects.
xupsEnvironmentFullGroup
The Full set of xupsEnvironment subgroup objects.
xupsAlarmFullGroup
The Full set of xupsAlarm subgroup objects.
xupsAlarmEventsFullGroup
The Full set of Alarm/Event history subgroup objects.
xupsTestFullGroup
The Full set of xupsTest subgroup objects.
xupsControlFullGroup
The Full set of xupsControl subgroup objects.
xupsConfigFullGroup
The Full set of xupsConfig subgroup objects.
xupsTrapControlFullGroup
The Full set of xupsTrapControl subgroup objects.
xupsRecepFullGroup
The Full set of xupsRecep subgroup objects.
xupsTopologyFullGroup
The Full set of xupsTopology subgroup objects.
xupsDeprecatedGroup
Contains objects which are now deprecated.