upsAdvConfigLowBatteryRunTime - ups Adv Config Low Battery Run Time - PowerNet-MIB

MIBs list

With IPHost Network Monitor you can run simple snmp requests against a Dell device in your network.

upsAdvConfigLowBatteryRunTime

ups Adv Config Low Battery Run Time
1.3.6.1.4.1.318.1.1.1.5.2.8

The desired run time of the UPS, in seconds, once the low battery condition is reached. Allowed values are 120, 300, 420, or 600 seconds. During this time the UPS will produce a constant warning tone which can not be disabled. If a value other than a supported value is provided in a set request, the UPS interprets the value as the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.

Back to PowerNet-MIB MIB page.